Remedial Measures for Continuous Slabs against Vibration: A Case Study
Neha Vivek A.1, Nimisha Nandakumar1, Sachin B.1, Hareesh M.2
1M. Tech Structural Engineering, School of Mechanical and Building Sciences, VIT University, Vellore-632014
2Assistant Professor (SMBS), School of Mechanical and Building Sciences, VIT University, Vellore-632014
*Corresponding Author Email: nehavivek93@gmail.com; nimishank1810@gmail.com;sachinb.15121992@gmail.com
ABSTRACT:
This paper reports the remedial measures to reduce floor vibrations caused due to human activities in an existing RCC commercial building. A case study is carried out in a building located at Chittoor, Andhra Pradesh, where reinforced concrete floor vibration is beyond human threshold limit. First, the design report of various RCC structural elements is cross verified and then the non destructive tests are conducted to assess the quality of concrete used for construction. From the acquired information, various remedial measures that are feasible to rehabilitate the building is analysed by analytical and numerical methods. Then, the suitable remedial measure in regard to structural behaviour and economy is recommended.
KEYWORDS: Floor Vibration, Remedial Measure, Natural Frequency.
INTRODUCTION:
Vibration is a mechanical phenomenon where oscillations occur about an equilibrium point. If frequency of oscillation is less, then vibration is felt causing discomfort to humans and if frequency is more, the vibration is not experienced. It is caused in structural floor system due to human activities (Ref. I and II), decreased damping, improper design of slab, earthquake loads, wind loads or other impact loads. The main focus in our case study is vibration caused due to human activities. Vibration has to be arrested for human comfort, to strengthen the slab and to avoid fatigue cracks.
In a G+4 Shopping Complex located at Chittoor, vibration is found to exceed the human threshold limit in the 2nd, 3rd and 4th floor causing discomfort to the occupants.
The slabs are designed using IS 456:2000 (Ref. VII) which specifies design criteria for spans up to 3.5m. But, in this building’s floor, the spans are greater than 3.5m for which the design is unreliable causing the vibration.
The objective of this paper is to identify the source of vibration and its characteristics and to recommend an appropriate and economical remedial measure to the floor under consideration.
PROBLEM OVERVIEW
The residents of the Shopping Complex felt a sense of discomfort when articles like cement bags (weighing about 50kgs) were dropped on the floor and also for activities such as jumping, running, etc. As a consequence of this, the vibrations are felt in this slab and also in its adjacent slabs (Ref. III and IV).
Figure 1- Existing Floor Plan (All dimensions in mm)
Figure 2- Reinforcement Details of Slab 2 under Consideration (All dimensions in mm)
EXISTING SLAB
Due to this problem, the design of slab is cross-verified and then non-destructive tests are conducted to assess the quality of concrete used.
Existing Slab Design
i. Data:
Grade of concrete = 25 MPa
Grade of steel= 415 MPa
Shorter span, Lx= 6.78 m
Longer span, Ly= 8.23 m
Lx/Ly = 1.21 > 2, Hence, it is a two-way slab.
ii. Depth of Slab:
Assume D= 175 mm
Clear cover, Cc= 20 mm
Therefore, d= 175-20= 155 mm
iii. Effective Span:
In the x- direction, it is the least of,
a. Lx=clear span + effective depth= 6.78+0.155=6.935 m
b. Lx=centre to centre of supports=
6.78+0.76= 7.54 m
Hence, Lx= 6.935 m
In the y- direction, it is the least of,
a. Ly= clear span + effective depth= 8.23+0.155= 8.39 m
b. Ly= centre to centre of supports=
8.23+0.61= 8.84m
Hence, Ly= 8.39 m
iv. Loads:
Self Weight= 0.175x25= 4.375 kN/m2
Super imposed Load= 5 kN/m2
Total service load= 9.375 kN/m2
Design Ultimate Load, Wu= 9.375x 1.5= 14 kN/m2
v. Ultimate Design Moments:
Referring Table 26 of IS 456: 2000 and taking the bending moment coefficients for Ly/Lx = 8.39/6.935 = 1.209, the maximum bending moments per unit width are as follows:
a. Negative Moment at Continuous Edge
Mux= αxWuLx2= 0.0483x14x6.9352= 32.52 kN-m
Muy= αyWuLx2= 0.037x14x6.9352= 24.91 kN-m
b. Positive Moment at Midspan
Mux= αxWuLx2= 0.0363x14x6.9352= 24.44 kN-m
Muy= αyWuLx2= 0.028x14x6.9352= 18.85 kN-m
Hence, Maximum Bending Moment from above is, Mu= 32.52 kN-m
vi. Check for depth:
Mu= 0.138fckbd2
Hence, d= √ (Mu/0.138fckb) = √(32.52x106/0.138x25x1000) = 97.09mm> 155mm. Hence, depth provided is safe.
vii. Check for Reinforcement:
Mu= 0.87 fy Ast d [1- (Astfy/bdfck)]
Mu= 32.52x106= 0.87x415xAstx155 [1- (Astx415/1000x155x25)]
Therefore, required area of steel, Ast,(Req) = 622.62 mm2
And provided area of steel, Ast,(Prov) = 785.4 mm2 (#10mm at 100mm c/c)
Ast,(Prov)>Ast,(Req) Hence, reinforcement provided is safe.
Non-Destructive Tests Results
Rebound hammer test and Ultrasonic Pulse Velocity test is conducted on the slabs, beams and columns of this building.
The result obtained by rebound hammer test is as follows:
1. The average values of compressive strength for second floor columns lie between 23.42 N/mm2 and 29.21 N/mm2 and as per drawing the grade of concrete is M25. Hence, the results show the average quality of concrete, which is not satisfactory.
2. The average values of compressive strength for third floor columns lie between 26.12 N/mm2 and 35.75 N/mm2 and as per drawing the grade of concrete is M25. The average values of compressive strength for third floor columns are satisfactory but compressive strength at few locations of column are less than 25 N/mm2, which is not satisfactory.
3. The average values of compressive strength for second floor roof beams and third floor roof beams lies between 25.15 N/mm2 and 31.97 N/mm2 and as per drawing the grade of concrete is M25. Hence, the compressive strengths of second floor roof beams are satisfactory.
4. The average compressive strengths of second floor roof slabs lies between 19.17 N/mm2 and 26.67 N/mm2 and as per drawing the grade of concrete is M25. Hence, the results show the average quality of concrete, which is not satisfactory.
5. The average compressive strengths of third floor roof slabs lie between 25.33 N/mm2 and 29.66 N/mm2 and as per drawing the grade of concrete is M25. Hence, the compressive strengths of third floor slabs are satisfactory.
The result obtained by Ultrasonic pulse velocity test is as follows:
1. The average values of UPV for second floor columns range from 1890 m/sec to 2500 m/sec. Hence the concrete integrity is qualitatively not good.
2. The mean value of UPV for third floor columns lies between 2990 m/sec to 3750 m/sec. In this floor most of the values obtained above 3250 m/sec. Indicates that the quality of concrete is medium.
3. The mean value of UPV for second and third floor roof slabs lies between 2490 m/sec to 3020 m/sec. The results indicate the concrete quality from integrity point is not appreciable.
4. The average values of UPV readings of second and third floor roof beams lies between 3290 m/sec to 3690 m/sec. The UPV values again show that the quality of concrete is medium in the third floor beams.
Figure 3- Rebound Hammer Test at Columns
Figure 4- Ultrasonic Pulse Velocity Test at Slabs
Figure 5-Ultrasonic Pulse Velocity at Columns
The level of the slab is measured with the help of levelling instruments and it is found that there is variation of level in slab. Also, core cutter samples are taken and it showed that, the thickness of slab 2 ranges from 145mm to 150mm instead of design depth of 175mm.
REMEDIAL MEASURES
The vibration control can be done by active methods or passive methods. The active methods include feedback control and collocated control. The passive methods include vibration isolation, dampers, altering structural design and other methods.
For the floor considered, there are various vibration control methods which can be adopted for this building like:
i. Over lay method
In this technique, a plain or reinforced concrete slab is overlaid on top or bottom of the existing slabs to increase the section dimension, in turn increasing the dead weight of the slab due to which vibration reduces. Since, the span of the slabs is very large, it is tedious and uneconomical to adopt this method.
ii. External post-tensioning
In this method, the reinforcements in the slab are post-tensioned to prevent vibration. The minimum grade of concrete required for post tensioning without concrete failure is M30. The grade of concrete used for this building is M25. Hence, this method cannot be recommended.
iii. Partitions walls
Provision of partition walls will increase the dead weight of the slab and they act as dampers to reduce floor vibration. The utility of that room is for a banquet hall which requires a large space without any partition walls in between. So, this method is not feasible.
iv. Reducing slab span
In a built RCC structure, reducing the slab span is a challenging task but then many a time this is an efficient remedial measure to overcome vibration and deflection problems. The reduction in slab span is possible by providing an intermediate beam to run between the girders. In this paper, this option is chosen and further analysis for vibration and methodology for the provision of intermediate beam is explained in detail in the following sections.
ANALYSIS USING STAAD.Pro
The adequacy of a floor system from the stand point of its vibration serviceability due to human activity, specifically excitation loads, can be assessed using STAAD.Pro (Ref. VI). The procedures of Chapters 3 and 4 of the AISC Steel Design Guide Series No. 11 - Floor Vibrations due to Human Activity (Ref. V) have been implemented.
The vibration calculation is done for beam or the joist mode and girder mode. The two modes are then combined to obtain the system frequency and other results of the combined mode using the Dunkerley relationship described in chapter 3 of the AISC Design Guide. Results for the 2 basic modes and the combined mode are provided in a tabular form.
The output for the combined mode consists of:
i. the peak acceleration for walking excitation
ii. allowable acceleration (known in the code as the acceleration limit)
The design criterion as stated in the code in the third paragraph in Chapter 4 is that if the peak acceleration is less than the acceleration limit, then the floor system is satisfactory against vibration.
Considering a thickness of concrete above flute as 50mm, the Natural Frequency, Peak Acceleration and Allowable Acceleration of the composite slabs are calculated using STAAD.Pro.
The floor is checked for vibration considering 20% live load which acts as a sustained load during vibration.
First, only one intermediate beam is provided in the slab considered as shown in Fig.6.
Figure 6-Floor plan with one intermediate beam
Table 1- Resultant Natural Frequency and Acceleration- Single Beam
|
Slab Name |
Natural Frequency (Hz) |
Peak Acceleration |
Allowable Acceleration Limit |
|
S1 |
7.869 |
0.0058 |
0.0050 |
|
S2 |
7.925 |
0.0059 |
0.0050 |
It is observed that the peak acceleration is more than the allowable acceleration limit. This shows that the vibration is not below the human threshold limit. So a continuous beam was provided as shown in the Fig.7.
Figure 7- Floor plan with one continuous intermediate beam (All dimension in mm)
Table 2- Resultant Natural Frequency and Acceleration- 1 Continuous Beam
|
Slab Name |
Natural Frequency (Hz) |
Peak Acceleration |
Allowable Acceleration Limit |
|
S1 |
10.395 |
0.0020 |
0.0050 |
|
S2 |
9.087 |
0.0022 |
0.0050 |
|
S3 |
8.225 |
0.0049 |
0.0050 |
|
S4 |
8.339 |
0.0052 |
0.0050 |
|
S5 |
7.990 |
0.0052 |
0.0050 |
|
S6 |
6.134 |
0.0028 |
0.0050 |
Here also it is observed that the peak acceleration is more than the allowable acceleration limit. Hence, two continuous beams are provided as shown in the Fig.8.
Figure 8- Floor plan with two continuous intermediate beams (All dimensions in mm)
Table 3- Resultant Natural Frequency and Acceleration- 2 continuous beams
|
Slab Name |
Natural Frequency (Hz) |
Peak Acceleration |
Allowable Acceleration Limit |
|
S1 |
10.406 |
0.0029 |
0.0150 |
|
S2 |
9.235 |
0.0033 |
0.0150 |
|
S3 |
8.264 |
0.0074 |
0.0150 |
|
S4 |
8.383 |
0.0080 |
0.0150 |
|
S5 |
8.00 |
0.0078 |
0.0150 |
|
S6 |
5.91 |
0.0042 |
0.0150 |
|
S7 |
11.75 |
0.0035 |
0.0150 |
|
S8 |
6.24 |
0.0033 |
0.0150 |
|
S9 |
11.57 |
0.0038 |
0.0150 |
|
S10 |
6.04 |
0.0034 |
0.0150 |
It is observed that the peak acceleration is less than the allowable acceleration limit. This shows that the vibration is reduced. So the provision of two intermediate continuous steel beams is the most appropriate measure to arrest the vibration in this floor.
COMPOSITE BEAM DESIGN
The composite Beam Design is done using the Euro Code- EN 1994-1-1-2005 (Ref. VIII). The design is as follows.
Slab Properties
The composite beam is assumed to be simply supported on beams B5. As per final revised drawing, the following data is considered for design. Fig. 11 shows the cross section of the composite slab.
Effective span, L= 6.78m
Thickness of Slab= 7”= 180 mm
Calculation of Loads
The Area of slab considered for load distribution on composite beam
= (6.78-4.115)*4.115/2+(4.115/2)^2= 9.72m2
Self weight of slab= 25*0.18= 4.5kN/m2
Floor finish load= 1.5kN/m2
Live load considered= 5kN/m2
Total load on slab= 11kN/m2
Slab load distributed as UDL to beam B5= (11*9.72*2)/6.78= 31.53kN/m
Self weight of steel beam (assumed)= 0.5kN/m
Total load on composite beam= 32 kN/m
Factored load on beam B5, W = 1.5*32 = 48kN/m
The maximum factored bending moment= WL2/8= 276 kN-m
Design for Flexure
Taking ISMB300 a trial section for the design, the effective width beff of concrete flange for simply supported beam is L/8 on each side of the web (from EN 1994-1-1, 2005) = (6.78/8)*2 = 1.695m
Approximating beff to=1600mm (Ref. Fig. 11)
Assuming full shear connection, the plastic stress distribution for composite beam as shown is considered for design.
Compressive Force=Tensile Force,
C= (0.85 ϕ fcbeff a) and T= (0.9 fyAst)
Now, depth of concrete under compression from top fibre,
a= (0.9 fyAst/ 0.85 ϕ fcbeff) = 62.05mm
Internal lever arm distance
= (Depth of steel beam/2 + thickness of slab – a/2) = 296.97mm
Plastic moment of resistance provided by concrete
= (0.85*0.6*25*62.05*296.97*1600) = 375.92kN-m
Plastic moment of resistance provided by steel
= (0.9*250*5626*296.97)= 375.92kN-m
The moment of resistance provided by concrete and steel are same and greater than the factored moment 276 kN-m. Hence the composite section is safe against bending.
Design for Shear
Vertical Shear
Factored vertical shear= WL/2= 163 kN
Nominal Plastic shear resistance under pure shear, Vp= (Aw*fy/sqrt(3)) = 301.09kN
Design shear strength of beam= Vp/1.1= 273.72kN
(d/tw) is less than (67*sqrt(250))/fy
Hence, web is safe against shear buckling.
Hence, the section ISMB300 is safe against vertical shear.
Since factored shear force is greater than 0.5 times of design shear strength of the beam, the reduced moment of resistance in bending= 360.883kN-m (EN 1994-1-1-2005).
Hence, the beam is safe against bending.
Horizontal Shear/ Shear Connectors
Total factored horizontal shear for 100% composite action
= (0.9*fy*area of ISMB300)= 1265.85kN
Assuming 16mm diameter stud bolt and ultimate tensile stress 400N/mm2
From Clause 6.6.3.1 of EN 1994-1-1-2005
Design shear resistance per stud head, PRD= (0.8 fuπd2/4)/1.25= 51.4458kN
PRD= 0.29 d2sqrt(fckEcm), α=1 for height of stud 120 mm= 58.692 kN
The lesser of PRD= 51.4458kN
Hence, number of shear studs required= 24.60nos.
Provide 28 nos. of 16mm diameter and 120mm height headed studs at 250mm c/c throughout the length of the beam.
Check for Deflection
Service load= 32.03kN/m
Moment of inertia for composite section by neglecting the concrete in tension zone
= 1.2E+09mm4
Deflection, δ= (5WL4)/(384EI)= 3.5mm
Permissible deflection= L/300= 22.6mm
Hence, safe against deflection.
Figure 9- Longitudinal Section of Composite Slab (All dimensions in mm)
Figure 10- Cross-Section of Composite Slab (All dimensions in mm)
Figure 11-Cross-Section of Composite Slab (All dimensions in mm)
To obtain a composite action between Slab and the Steel Beam provided, they are connected using shear studs as shown in Fig. 9. To counteract the hogging moment, the top surface of slab is chipped off by 40mm and additional reinforcements are provided perpendicular to the steel beam and concrete layer is laid.
The existing building’s plan, section and reinforcement drawing details are obtained and the maximum moment and torsion that can be taken up by the beams and columns are calculated. It is found that the moments and torsion produced after the provision of intermediate steel beams are well within the permissible limits.
COST ESTIMATION
Table 4- Abstract of Cost
|
Sl. No. |
Component |
Unit |
Rate |
Quantity |
Total cost |
|
1. |
Concrete |
m3 |
5000 |
3 |
15000 |
|
2. |
ISMB300 Steel section |
ton |
2000000 |
0.05 |
100000 |
|
3. |
10mm diameter HYSD bars |
ton |
30000 |
0.65 |
19500 |
|
4. |
M16 4.6 grade bolts |
ton |
65000 |
0.08 |
5200 |
|
5. |
M20 4.6 grade bolts |
Ton |
67000 |
0.05 |
3350 |
|
6. |
Anchor plates |
Ton |
43000 |
0.0150 |
6450 |
|
7. |
Labour costs |
- |
- |
- |
75000 |
|
8. |
Miscellaneous |
- |
- |
- |
60000 |
|
GRAND TOTAL (for one floor) approx. |
285000 |
||||
The total approximate cost for one floor is Rs.2,85,000/-.
The total approximate cost to provide intermediate steel beams for 3 floors is Rs. 8,55,000/-.
RESULTS AND DISCUSSION:
The problem due to which vibration is caused in the floor slabs of the building is identified by cross verifying the design and also by carrying out Non-
Destructive Tests like Rebound Hammer Test, Ultrasonic Pilse Velocity Test, etc.
Various appropriate vibration control methods like overlay method, external post tensioning, provision of partition walls and reducing the span of the slab are considered. The most appropriate method is to reduce the floor vibration in the present building under study is to reduce the span of the slab by introducing intermediate steel beam that ensures composite action with the concrete deck.
STAAD. Pro software is used to model the floor with composite beam and study the vibration characteristics. Different options for providing intermediate steel beam are studied and the final safer option is reported as shown in Fig.8. Then the required steel section is designed as per EN 1994-1-1-2005. Then the schematic structural detailing drawing for the construction is also reported as shown in Fig.9 and Fig.10.
CONCLUSIONS:
The case study is on a building that is already constructed. The span of the considered slab is 6.78m which is greater than 3.5m, hence the serviceability criteria is governed by vibration. The slab undergoes vibration above human threshold level which was felt by the occupants. A possible remedy is to provide two continuous steel beams. According to the results obtained above, we can conclude that the vibration of floor system maybe brought down after providing two intermediate steel beams ISMB300 as shown in Fig.8.
FUTURE SCOPE OF WORK:
The Indian code specifies the serviceability conditions for the spans less than 3.5m in which the governing factor for design is deflection but when the span of the slabs exceed this limit, consideration of vibration as serviceability criteria becomes important. The future scope of work can be done in studying and suggesting suitable guidelines when the minimum span of slab exceeds 3.5m.
ACKNOWLEDGEMENT:
We avail this opportunity to express our gratitude and appreciation to VIT University for providing us with equipments and facilities. We are very much privileged to express our profound gratitude to Prof. Sekar S. K. and Prof. Abdul Rahim A. for their guidance and encouragement throughout the project. We would also like to acknowledge NICMAR, Hyderabad for giving us an opportunity to participate in IACCM 2015.
REFERENCES:
1. Allen D. E. – “Building Vibrations From Human Activities”, ACI, Concrete International: Design and Construction.
2. Allen, D. E., and Murray, T. M., (1993) “Design Criterion for Vibrations Due to Walking,” Engineering Journal, Fourth Quarter, American Institute of Steel Construction, 1993.
3. Farzad Naeim – “Design Practise To Prevent Floor Vibrations”, Structural Steel Education Council, 1991.
4. Murray T. M.- “Design To Prevent Floor Vibration”, Engineering Journal, AISC, Vol.12, No.3, 1975.
5. Thomas M. Murray, David E. Allen, Eric E. Ungar – “Floor Vibrations Due to Human Activity”, American Institute of Steel Construction, Steel Design Guide Series No. 11, Inc., 2003.
6. STAAD. Pro, V8i (SELECT series 6) 20.07.11.33
7. IS 456:2000- Plain and Reinforced concrete- Code of practice.
8. Euro Code- (EN 1994-1-1-2005).
|
Received on 12.11.2015 Accepted on 25.12.2015 © EnggResearch.net All Right Reserved Int. J. Tech. 5(2): July-Dec., 2015; Page 77-85 DOI: 10.5958/2231-3915.2015.00001.2 |
|